INSTALLATION INFORMATION
29.
See Drawing 164201603-7 for UPM terminal locations and Table K, Table L, or Table M for
termination requirements.
30.
Setup of the CAN Bridge card for parallel operation must be performed by an authorized
Eaton Customer Service Engineer . Contact service to schedule a date.
31.
For parallel system circuit breaker ratings, see appropriate information in Table R.
32.
For parallel system ratings, see the appropriate information in Table S through Table V.
Table R. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
UPM
Model
9390-40/20
9390-40/30
9390-40/40
9390-80/40
9390-80/50
9390-80/60
9390-80/80
A-28
EATON Powerware
Circuit Breaker Ratings
Configuration
208V/220V
MOB
1+1
150
2+0 and 2+1
150
3+0 and 3+1
150
4+0
150
1+1
200
2+0 and 2+1
200
3+0 and 3+1
200
4+0
200
1+1
225
2+0 and 2+1
225
3+0 and 3+1
225
4+0
225
1000
1+1
300
2+0 and 2+1
300
3+0 and 3+1
300
1000
4+0
300
1200
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Output Voltage
380V/400V/415V
MIS
MBP
MOB
MIS
150
150
90
300
300
90
450
450
90
600
600
90
200
200
110
350
350
110
600
600
110
700
700
110
225
225
125
500
500
125
700
700
125
1000
125
300
300
150
600
600
150
1000
150
1200
150
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
REVISION:
C
S
164201603 Rev 2 www.powerware.com
480V
MBP
MOB
MIS
90
90
70
200
200
70
150
300
300
70
200
400
400
70
250
110
110
80
225
225
80
175
350
350
80
250
450
450
80
350
125
125
100
100
250
250
100
200
400
400
100
300
500
500
100
400
150
150
125
125
300
300
125
250
450
450
125
400
600
600
125
500
164201603-5
DATE:
071608
MBP
70
70
150
200
250
80
80
175
250
350
100
200
300
400
125
250
400
500
SHEET:
18 of 23