Eaton 93PM UPS 30–200 kVA
9.2
Rated input voltage
Voltage tolerance (Rectifier input)
Voltage tolerance (Bypass input)
Rated input frequency
Frequency tolerance
Number of input phases (rectifier & bypass) 3 phases, + N
Input power factor
Rated/maximum mains input current
Input current distortion at rated input cur-
rent, iTHD
Rectifier ramp-up, rectifier start and load
step
Backfeed protection
9.3
Table 23: Eaton 93PM 30–200 kW UPS system output
Number of output phases
Rated output voltage
Rated output frequency
Total voltage harmonic distortion:
100 % linear load
100 % non-linear load
Rated output frequency
Output frequency variation
Slew rate
Output current
Overload capability at
ambient 40 °C
(on inverter)
©
Eaton Corporation plc 2017. All rights reserved.
UPS system input
UPS system output
220/380 V; 230/400 V; 240/415 V
230 V -20% / +20%
230 V -15% / +10%
50 or 60 Hz, user configurable
40 to 72 Hz
0.99
9
See Tables
30 kW: < 4,5%
40–200 kW, 60 kVA: < 3%
10 A/s (default), configurable.
Min 1 A/s
Yes, for rectifier and bypass lines
3 phases + N
220/380 V; 230/400 V;
240/415 V; configurable
50 or 60 Hz, user
configurable
< 1%
< 3%
50 Hz or 60 Hz, configurable
±0.1 Hz
0.4 Hz/s
8
See Table
10 min 102–110% load
60 s 111–125% load
10 s 126–150% load
300 ms > 150% load
Revision: 005
Document ID: P-164000249
User's and installation guide
11
and
10
and Table
112 (126)