Eaton Powerware 9390 Installation And Operation Manual page 151

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

1.
The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201603-9.
2.
The UPS cabinet is palleted separately for shipping.
3.
Do not tilt cabinets more than
4.
Dimensions are in millimeters (inches).
5.
The cabinet can be installed in line‐up‐and‐match or standalone configurations.
Table A. UPS Cabinet Weight
Model
Powerware 9390-40/20
Powerware 9390-40/30
Powerware 9390-40/40
Powerware 9390-80/40
Powerware 9390-80/50
Powerware 9390-80/60
Powerware 9390-80/80
EATON Powerware
"
10° during handling.
Voltage
Input
Output
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
208V/220V
208V/220V
380V/400V/
380V/400V/
415V/480V
415V/480V
DESCRIPTION:
DRAWING NO:
REVISION:
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Weight
kg (lb)
Shipping
Installed
231 (508)
208 (458)
231 (508)
208 (458)
231 (508)
208 (458)
313 (690)
290 (640)
271 (618)
258 (568)
313 (690)
290 (640)
271 (618)
258 (568)
313 (690)
290 (640)
271 (618)
258 (568)
313 (690)
290 (640)
271 (618)
258 (568)
PHYSICAL FEATURES AND REQUIREMENTS
164201603-2
DATE:
C
S
164201603 Rev 2 www.powerware.com
INSTALLATION INFORMATION
Point Loading
4 at 52.2 (115)
4 at 52.2 (115)
4 at 52.2 (115)
4 at 72.5 (160)
4 at 64.5 (142)
4 at 72.5 (160)
4 at 64.5 (142)
4 at 72.5 (160)
4 at 64.5 (142)
4 at 72.5 (160)
4 at 64.5 (142)
SHEET:
1 of 2
071608
A-3

Advertisement

Table of Contents
loading

Table of Contents