Eaton Powerware 9390 Installation And Operation Manual page 164

20-80kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

INSTALLATION INFORMATION
Table J. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390-80/80
Basic Unit Rating at 0.9 lagging pF load
Input and Bypass Input
Output
AC Input to UPS Rectifier
(0.98 min. pF)
Full Load Current plus Battery
Recharge Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral-if required, (1)
Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)
NOTE
A-16
EATON Powerware
VOLTS
VOLTS
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps@
(2.0V/cell)
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
AWG or kcmil
-
(each)
Callout letters A , B , C , and D map to Drawing 164201603-4, sheets 1 of 5,
3 of 5, 4 of 5, and 5 of 5.
®
9390 UPS (20–80 kVA) Installation and Operation Manual
Units
kVA
80
kW
72
208/220
208/220
240
2/0
(2)
222/210
2/0
(2)
Vdc
384-480
432-480
203
3/0
(1)
222/210
2/0
(2)
1/0
(1)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201603-5
REVISION:
D
S
164201603 Rev 2 www.powerware.com
Rating 50/60 Hz
80
80
80
72
72
72
380
400
415
380
400
415
135
130
125
2/0
2/0
2/0
(1)
(1)
(1)
122
116
111
2/0
2/0
2/0
(1)
(1)
(1)
432-480
432-480
203
203
203
3/0
3/0
3/0
(1)
(1)
(1)
122
116
111
2/0
2/0
2/0
(1)
(1)
(1)
6
6
6
(1)
(1)
(1)
SHEET:
DATE:
071608
80
72
480
480
105
1/0
(1)
96
1/0
(1)
432-480
203
3/0
(1)
96
1/0
(1)
6
(1)
6 of 23