Access Control Menu - Eaton Network Management Card User Manual

Network management card
Hide thumbs Also See for Network Management Card:
Table of Contents

Advertisement

------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings - Master
------------------------------------------------------------------------
1 : Name [Master]
2 : Shutdown if remaining time under (sec) [180]
3 : Shutdown if capacity under (%) [20]
4 : Shutdown timer enabled (0=No, 1=Yes) [0]
5 : Shutdown timer (sec) [1800]
6 : Shutdown duration (sec) [120]
7 : Restart if capacity exceed (%) [0]
0 : Exit
------------------------------------------------------------------------
------------------------------------------------------------------------
NETWORK MANAGEMENT CARD
Shutdown settings – Outlet #1
------------------------------------------------------------------------
1 : Name [Group1]
2 : Switch off after (sec) [2147483647]
3 : Switch off if capacity under (%) [0]
4 : Shutdown duration (sec) [120]
5 : Switch on after (sec) [0]
0 : Exit
------------------------------------------------------------------------
6.3.8

Access Control menu

This menu defines the accessibility of the card by a client.
Network Management Card
– User Manual
34003991XT_EN/EF
Page
88/127