Eaton 34003991EN/EB User Manual
Eaton 34003991EN/EB User Manual

Eaton 34003991EN/EB User Manual

Network management card
Table of Contents

Advertisement

www.eaton.com
Network Management Card
– User Manual
Network
Management Card
User manual
34003991EN/EB
Page
1/118

Advertisement

Table of Contents
loading

Summary of Contents for Eaton 34003991EN/EB

  • Page 1 Network Management Card – User Manual Network Management Card User manual 34003991EN/EB Page 1/118...
  • Page 2: Table Of Contents

    PTIMISING THE PERFORMANCE OF YOUR BROWSER 4.2.1 UPS properties page 4.2.2 On-line help 4.2.3 UPS control 4.2.4 UPS weekly schedule programming 4.2.5 Shutdown parameters 4.2.6 Measurements 4.2.7 Event log 4.2.8 System log OTIFICATION Network Management Card – User Manual (NMC) ANAGEMENT 34003991EN/EB Page 2/118...
  • Page 3 RS232 link configuration and connection 7.2.2 RS485 link configuration and connection 7.2.3 Configuration of the JBUS/MODBUS communication parameters DDITIONAL EB PAGES Network Management Card – User Manual SHUTDOWN SEQUENCES 2 NMC BOARDS OGIN ASSWORD TO EFAULT ONFIGURATION 34003991EN/EB Page 3/118...
  • Page 4 ABLES OF ALARMS AND EVENTS 8.1.1 Table of alarms 8.1.2 Table of UPS events 8.1.3 Table of system alarms SNMP OBJECTS 8.2.1 MGE MIB 8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11) GLOSSARY Network Management Card – User Manual 34003991EN/EB Page 4/118...
  • Page 5: Eaton Network Solution

    - Supervision of the UPSs over the Network : Web browser, Enterprise Power Manager, or SNMP NMS. - Protection of the computers (multi-platform) with : Network Shutdown Module for MGE Office Protection Systems UPS. Netwatch for Powerware UPS. - Connexion of the UPS to the Network. Network Management Card – User Manual 34003991EN/EB Page 5/118...
  • Page 6: Connecting The Ups To The Ethernet Network

    Continuously waits for information from the Network Management Card/Proxy connected to the UPS. Warns administrators and users if AC power fails and proceeds with graceful system shutdown before the end of battery backup power is reached. Network Management Card – User Manual 34003991EN/EB Page 6/118...
  • Page 7: Supervision Of The Upss Over The Network

    Connect the UPS to a wall outlet. (For UPSs above 3kVA, please refer to the UPS installation manual). Connect the power cord of each computer to an outlet on the UPS. (For UPSs above 3kVA, please refer to the UPS installation manual) Network Management Card – User Manual 34003991EN/EB Page 7/118...
  • Page 8: Presentation Of The Network Management Card (Nmc)

    They also supply alarms to the Network Shutdown Modules to trigger shutdown or other automatic actions for protected servers. Network Management Card – User Manual for the MGE Office Protection Systems UPS. for the Powerware UPS. 34003991EN/EB download.mgeops.com Page 8/118...
  • Page 9: Direct Sending Of E-Mail

    Environment Sensor enables measurement of temperature and humidity around the UPS, consideration of external alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (see Status Environment Configuration) Network Management Card – User Manual E-mail message settings) Applications” 34003991EN/EB Environmen Page 9/118...
  • Page 10: Technical Data

    EMC: 89/336/EEC and 93/68/EEC. 1.3.3 Configuration The user can configure the card with one of the following means: Web browser Local serial link (network parameters) BOOTP/DHCP (network parameters). Network Management Card – User Manual complies with the following standards: 34003991EN/EB Page 10/118...
  • Page 11: Administration

    High and low thresholds, hysteresis and offset adjustable via Web interface. Possibility of notification of status changes by e-mail, SMS or SNMP trap. Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m). Name and status of each configurable contact. Network Management Card – User Manual 34003991EN/EB Page 11/118...
  • Page 12: Mib (Management Information Base)

    Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m) Hot installation 1.3.7 MIB (Management Information Base) Compatible with MIB MGE Office Protection Systems V1.7 The list of objects managed can be found in the Network Management Card – User Manual appendix 34003991EN/EB Page 12/118...
  • Page 13: Default Parameters

    Accept automatic update from NSM or EPM ntpserver 9600 baud without without – User Manual 34003991EN/EB Possible value Network IP address Network IP address Network IP address Active / Deactivated Active / Deactivated 49 characters maximum 49 characters maximum 31 characters maximum 10 to 99999 sec.
  • Page 14: Installation

    2 Installation 2.1 Unpacking and check on contents The installation kit contents: A Network Management Card (66102) A serial communication cable for configuration (34003918) Installation manual (34003905) 2.2 Indications Network Management Card – User Manual 34003991EN/EB Page 14/118...
  • Page 15: Installation In The Ups

    Port operating at 100Mbits/s. Description Card startup in progress. Communication with UPS in progress Normal operation. Communication with the UPS is operational Configuration menu is active Normal operation. Configuration menu is deactived Communication with the Environment Sensor (option). 34003991EN/EB Page 15/118...
  • Page 16: Sensor Installation (Option)

    It is connected to the Service port (Settings/Sensor) directly on the Network Management Card with a standard Ethernet cable (20 meters maximum). Recognition is automatic. Supervision and configuration are performed via a menu that can be accessed directly from the home page. Network Management Card – User Manual 34003991EN/EB Page 16/118...
  • Page 17: Configuration

    Enter admin. The main menu is displayed: ----------------------------------------------------------------------------- EATON NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration 3 : Set Login Password to Default 4 : Return to Default Configuration 0 : Exit ----------------------------------------------------------------------------- Network Management Card – User Manual 34003991EN/EB Page 17/118...
  • Page 18: Your Network Is Equipped With A Dhcp Server

    Note: As long as the card is not connected to the network, it continuously attempts to make connection. Once the connection has been established, the operational mode presented in the table above becomes effective. Network Management Card – User Manual 34003991EN/EB Page 18/118...
  • Page 19: Your Network Is Not Equipped With A Dhcp Server

    From a station connected to the same subnet as the card, open a web browser and enter the IP address of the card in the address field Check the display of the home page. Network Management Card – User Manual 34003991EN/EB Page 19/118...
  • Page 20: Supervision And Administration By Browser

    To view status changes on the UPS in real time, the browser must be configured so that it automatically refreshes all the objects on the current page. Example on IE 6: Tools / Internet Options / General / Parameters menu, tick Every time this page is visited and validate. Network Management Card – User Manual 34003991EN/EB Page 20/118...
  • Page 21: Ups

    “UPS Modules”: (available on modular UPS) to view general information on each modules. “About your UPS”: provides information on the UPS and the card, in particular, the model range and software version. These different pages are detailed in the following chapters. Network Management Card – User Manual 34003991EN/EB Page 21/118...
  • Page 22 The synoptic drawing depends on the UPS topology. The different drawings are described in the table below. UPS with automatic bypass UPS with automatic and manual bypass Network Management Card – User Manual "System" page. Normal operation Alarm present. This icon links directly to the alarm page. Loss of communication with the UPS 34003991EN/EB Page 22/118...
  • Page 23 AC to DC Converter: Network Management Card – User Manual In tolerances Out of tolerances AC to DC converter powered by AC Normal AC to DC converter not powered by AC Normal Powered Not powered Internal failure 34003991EN/EB Page 23/118...
  • Page 24 DC to AC converter powered by battery DC to AC converter not powered by battery Energy flow present No energy flow Powered Not powered Internal failure Energy flow present No energy flow In tolerances Out of tolerances 34003991EN/EB Page 24/118...
  • Page 25 AC Output : Network Management Card – User Manual Energy flow present No energy flow Powered Not powered Internal failure Energy flow present No energy flow Open Closed Energy flow present No energy flow Load protected Load not protected 34003991EN/EB Page 25/118...
  • Page 26 Boxes showing measurements appear when synoptic elements are hovered by the pointer. See example below. These measurements are available for AC to DC converter, Battery, DC to AC converter and automatic bypass. The measurements available in these boxes depend on the UPS range. Network Management Card – User Manual 34003991EN/EB Page 26/118...
  • Page 27 – OK: the test was completed correctly – NOK: the battery needs to be checked – Deactivated: the automatic battery test is not validated on the UPS Network Management Card – User Manual Outlet powered Outlet not powered or not protected 34003991EN/EB Page 27/118...
  • Page 28 The redundancy lost can generate Email notification (if set in the email notification page) and SNMP trap. It can also be used by NSM for server protection criteria. The Module Nr gives the location of the module in the UPS. Network Management Card – User Manual 34003991EN/EB Page 28/118...
  • Page 29 When the module is working properly with no alarms, the icon is not reactive, otherwise it is reactive and clicking on it makes the page Alarm Table appear. "Output load level": Value of the percentage of load at module output "Battery load level": Percentage of charge available in the battery module Network Management Card – User Manual 34003991EN/EB Page 29/118...
  • Page 30: Viewing The Alarms

    Click on "Alarm Table" scroll list to view the list of current alarms. The table of managed alarms is included in the appendix. The level of the alarms appears like below: Critical Warning Unknown Alarm table for standard UPS Network Management Card – User Manual 34003991EN/EB Page 30/118...
  • Page 31 Alarm table for modular UPS Network Management Card – User Manual 34003991EN/EB Page 31/118...
  • Page 32 4.2.1.5 Viewing the “About your UPS” window Click on "About your UPS" scroll list to view the information about the UPS and the card. Network Management Card – User Manual 34003991EN/EB Page 32/118...
  • Page 33: On-Line Help

    On-line contextual help in English is available at the top of each page by clicking on the Help link, which is always located on the top right corner. The navigation menu of the on-line help is identical to that of the card's pages. The Help page always opens a new window. Network Management Card – User Manual 34003991EN/EB Page 33/118...
  • Page 34: Ups Control

    These two fields do not travel "decoded" on the IT network. They are encrypted with an MD5 type algorithm, ensuring total confidentiality. In the event of password loss, the user can return to the default values via the maintenance menu. Network Management Card – User Manual 34003991EN/EB Page 34/118...
  • Page 35 Finally, the restart sequence is launched at the end of the time delay specified in the "Toggle duration" parameter. The output status is updated. Network Management Card – User Manual for the UPS main output and controlled outlets. 34003991EN/EB Page 35/118...
  • Page 36 The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card. Security: The administrator must click on Save and enter his/her login/password to save modifications or run commands. The default login and password by default are: admin/admin Network Management Card – User Manual 34003991EN/EB Page 36/118...
  • Page 37: Ups Weekly Schedule Programming

    The On / Off sequences are valid only if the card's time has been properly set. Security: The administrator clicks on "Save" and enters his/her login / password to save any edits. The login and password by default are: admin/admin Network Management Card – User Manual 34003991EN/EB Page 37/118...
  • Page 38: Shutdown Parameters

    The Output column enables each outlet to be named (maximum 20 characters). Note As priority is given to the main outlet, the card cannot supply the controlled outlets when main outlet power is off. Network Management Card – User Manual 34003991EN/EB Page 38/118...
  • Page 39 Important: Certain UPSs do not support this option Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The login and password by default are: admin/admin Network Management Card – User Manual shutdown sequence. 34003991EN/EB Page 39/118...
  • Page 40: Measurements

    "Save Log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type spreadsheets) "Clear Log" enables deletion of all records. Enter the login/password to validate this action. Network Management Card – User Manual "System" page (60 seconds by default). Approximately 435 34003991EN/EB Page 40/118...
  • Page 41: Event Log

    "Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this action. The card can save 435 events. The table of managed alarms is included in the Network Management Card – User Manual appendix 34003991EN/EB Page 41/118...
  • Page 42: System Log

    "Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this action. The card can save 435 events. The table of managed alarms is included in the appendix. Network Management Card – User Manual 34003991EN/EB Page 42/118...
  • Page 43: Notification

    4.3.1 Email Notification The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobile telephone transfer systems using text messages (SMS). Network Management Card – User Manual 34003991EN/EB Page 43/118...
  • Page 44 Network Settings: enables the name of the SMTP server to be entered. Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The default login and password are: admin/admin Network Management Card – User Manual recipientx@domain.com See page 34003991EN/EB Page 44/118...
  • Page 45: E-Mail Message Settings

    - UPS location recalls the geographic location of the UPS (see System Settings); it may or may not be selected. - Event message identifies the event generating the e-mail; it may or may not be selected. Message text is a free zone long of 255 characters maximum. Network Management Card – User Manual E-mail notification). 34003991EN/EB Page 45/118...
  • Page 46 - The date and time of the event, as saved in the log. - URL of the card, enabling a direct link with the card to be established. - Attachments, as configured for the e-mail recipients .- duplication of the subject, as configured. Network Management Card – User Manual 34003991EN/EB Page 46/118...
  • Page 47: C Onfiguration

    These two fields do not travel "decoded" on the IT network. They are encrypted with an MD5 type algorithm, ensuring total confidentiality. In the event of password loss, the user can return to the default values via the maintenance menu. Network Management Card – User Manual 34003991EN/EB Page 47/118...
  • Page 48: Network Settings

    If no response is received from the server, the card boots with the last saved parameters from the previous start. These parameters are those shown on the page. The default value for this parameter is "Enable" Note 1: Network Management Card – User Manual 34003991EN/EB Page 48/118...
  • Page 49 Important note: The card must be rebooted after any changes to these parameters.. Security: The administrator has to click on Save and enter his/her login/password to save any modifications. Network Management Card – User Manual See "System" page 34003991EN/EB Page 49/118...
  • Page 50: System

    Reset Communication button: performs a remote reboot of the card without modifying the configuration. This action is compulsory for consideration of any changes made on the "Network Settings" page. Security of this operation is ensured by requesting Login and Password. Network Management Card – User Manual UPS properties pages. 34003991EN/EB Page 50/118...
  • Page 51 IP address, subnet mask, gateway and BootP/DHCP value are maintained if the "Keep TCP/IP parameters" option is selected. Security of this operation is ensured by requesting Login and Password. The default login and password are : admin/admin Network Management Card – User Manual 34003991EN/EB Page 51/118...
  • Page 52: Notified Applications

    Application Name : Gived by the application at subscription time. Output: number of the UPS output from which the client is powered. Configuration: shows where the parameters of the Network Shutdown Module come from: Local (coming from the Network Management Card – User Manual 34003991EN/EB Page 52/118...
  • Page 53 Both buttons open a new window where it is possible to enter the Application name, the Hostname or IP Address, the Trap community and the severity. The default severity value is 1 – Warning Network Management Card – User Manual is available by clicking on the Configuration link. 34003991EN/EB Page 53/118...
  • Page 54: Central Shutdown Configuration

    In this page, select the NSMs for which you want to apply the new configuration. Press the "Remove" button. The NSMs selected will disconnect then reconnect and use the new configuration. Network Management Card – User Manual 34003991EN/EB Page 54/118...
  • Page 55: Access Control

    Authentication for configuration: Only the configuration pages are protected by login / password Full authentication: All pages are protected by login / password SSL and full authentication: All pages are protected by login / password and are only accessible in SSL Network Management Card – User Manual 34003991EN/EB Page 55/118...
  • Page 56 Connections with Network Shutdown Modules stay in standard mode (secure TCP) SSL Security Implementation: version 3.0 version 1.0 Method TLS_RSA_WITH_512_MD5 Auth Key Exchange Encryption RC4_512 Digest Changes take effect after a card reboot Network Management Card – User Manual 34003991EN/EB Page 56/118...
  • Page 57: Date And Time

    Accept automatic update from NSM or EPM: Enables initialisation of the date and time of the card, with the values provide by the Network Shutdown Modules or the Enterprise Power Management. Network Management Card – User Manual 34003991EN/EB Page 57/118...
  • Page 58 The even the card is used in a UPS supporting time-stamping, the card's time is automatically synchronized with that of the UPS. Note 2: After start-up, if the card is in manual mode or if no NTP server was reached, the card initializes at 01/01/1970 Network Management Card – User Manual 34003991EN/EB Page 58/118...
  • Page 59: Firmware Upload

    To upload a new version of the card's firmware, select the file to be loaded using the "Browse…" button and click Upload. Do not interrupt the operation before the card displays the following screen: Network Management Card – User Manual 34003991EN/EB Page 59/118...
  • Page 60: Characteristics

    Possibility of shutting down the installation safely if one of the thresholds is exceeded or dry contact status change Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum card/sensor distance: 20m) Network Management Card – User Manual 34003991EN/EB reset the card. Page 60/118...
  • Page 61: Environment Status

    The position is displayed with the parameters entered in the Environment Settings page. The last status change of each contact is time-stamped. The Internet browser updates this page every 10 seconds Network Management Card – User Manual 34003991EN/EB Page 61/118...
  • Page 62: Environment Settings

    Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. The default value is The high alarm disappears when the value drops below the High threshold - Hysteresis value Network Management Card – User Manual 34003991EN/EB Page 62/118...
  • Page 63 Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration information. Security: The user must be identified to access this page. Network Management Card – User Manual e-mail notification 34003991EN/EB page) Page 63/118...
  • Page 64 The user can Save the log on his/her workstation at any time, in a CSV format file. The user can also Clear the files contained in the card to reset the log. Network Management Card – User Manual 34003991EN/EB Page 64/118...
  • Page 65: Server Protection

    Network Management Card – User Manual list and sends its essential data: parameters) page to manage UPS shutdowns without affecting any of parameters), the first criterion encountered will launch the shutdown 34003991EN/EB notified applications. Page 65/118...
  • Page 66 The card does not accept values less than that programmed in the UPS. Check the UPS documentation. Network Management Card – User Manual Start of the shutdown sequence Shutdown after : Delay before shutdown Remaining autonomy Shutdown duration Card parameters 34003991EN/EB UPS Shut off If remaining time under UPS parameters Page 66/118...
  • Page 67: Shutdown When Backup Time Is Less Than

    The protection application transmit their own "Shutdown duration" to the Network Management Card. Based on these values (maximum Shutdown duration of all subscribed customer systems) that the card will send to the delayed shutdown order to the UPS. Network Management Card – User Manual 34003991EN/EB Page 67/118...
  • Page 68: Controlled Outlets

    It is possible to specify values for both criteria. The first criterion reached will initiate server shutdown. Network Management Card – User Manual Start shutdown main output outlet 1 Shutdown duration main output Shutdown duration outlet Shutdown duration 1 Shutdown duration 2 Shutdown duration 3 www.mgeops.com 34003991EN/EB Utility restore section “Downloads – Software Page 68/118...
  • Page 69: T He Different Server And Ups Shutdown Sequences

    - Low Battery Level - Low Battery Delay Network Management Card – User Manual page), the shutdown of all servers is initiated, followed by the UPS Start shutdown main output Shutdown duration main output Shutdown duration output 1 34003991EN/EB Utility restore Page 69/118...
  • Page 70: Case Of Power Restoration Before The End Of The "Shutdown Duration" Counter

    Shutdown duration Battery capacity under: Shutdown duration output 1 Battery capacity under: (output 1) Start shutdown main Utility restore output Shutdown Forced Reboot duration Battery capacity under Shutdown duration output 1 Battery capacity under: (output 1) 34003991EN/EB Utility restore Page 70/118...
  • Page 71: S Hutdown Management With 2 Nmc Boards

    If the settings are not the same, the first criteria reached on one the 2 cards will launch the secure shutdown of all servers Please, note that in any case the shutdown of the protected servers will be executed safely. Network Management Card – User Manual 34003991EN/EB Page 71/118...
  • Page 72: Configuration Via Rs232

    The menu is in English only. ----------------------------------------------------------------------------- EATON NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration 3 : Set Login Password to Default 4 : Return to Default Configuration 0 : Exit ----------------------------------------------------------------------------- Network Management Card – User Manual 34003991EN/EB Page 72/118...
  • Page 73: Choice 1: Restart / Reset

    6.2.1 Choice 1: Read Network settings Enables reading of the card's routine settings Network configuration : MAC address : 00:20:85:FD:1C:07 Mode : Static IP IP address : 166.99.18.129 Subnet mask : 255.255.248.0 Gateway : 166.99.17.1 Network Management Card – User Manual 34003991EN/EB Page 73/118...
  • Page 74: Choice 2: Modify Network Settings

    Wait during the new setting is saved ... Reset the card to take into account the new configuration. The card must be restarted in order for the new parameters to be taken into account. Network Management Card – User Manual 34003991EN/EB Page 74/118...
  • Page 75 Login Password are succefully been set. The card is now accessible via the Web with the password admin. The card must be restarted in order for the new parameters to be taken into account. Network Management Card – User Manual 34003991EN/EB Page 75/118...
  • Page 76: C Hoice 4: R Eturn To D Efault C Onfiguration

    Configuration has been set to default one. You must Reset the card. The card must be restarted in order for the new parameters to be taken into account. Network Management Card – User Manual of all the card’s parameters 34003991EN/EB Page 76/118...
  • Page 77: Industrial Network Management Card (Inmc Option)

    2 wires or 4 wires RS485 link are available. Warning: RS232 and RS485 communication ports cannot be used together. JBUS/MODBUS communication is operational 2 minutes after the startup of the card. Network Management Card – User Manual 34003991EN/EB Page 77/118...
  • Page 78: Technical Characteristics

    - without parity - Slave nr 1 - Rx on pin 1 - Tx on pin 3 - No termination 34003991EN/EB Possible values - 1200, 2400, 4800, 9600 - Without parity, even parity - 1 to FF (hexadecimal) - Rx on pin 1...
  • Page 79: I Nstallation

    7.2 Installation 7.2.1 RS232 link configuration and connection Set the SA2 switches like below: The next figure shows the details of the connection in RS232 mode: Network Management Card – User Manual 34003991EN/EB Page 79/118...
  • Page 80: Rs485 Link Configuration And Connection

    Use shielded cable in heavy industrial environments. Network Management Card – User Manual Pin number Function R- : Receiver - (input) R+ : Receiver + (input) T- : Transmitter - (output) T+ : Transmitter + (output) and capacitance 42pF/m) 34003991EN/EB Page 80/118...
  • Page 81 4: connection T- to R- (2 wires configuration) if set to ON 5: connection T+ to R+ (2 wires configuration) if set to ON 6: reserved 7: reserved 8: link termination between R+ and R- if set to ON Network Management Card – User Manual 34003991EN/EB Page 81/118...
  • Page 82: Rs485 Link Configuration For 2 Wires Connexion

    7.2.2.2 RS485 link configuration for 2 wires connexion Set the SA2 switches like below to set the RS485 mode: Set the SA1 switches to select the two wires configuration with no termination: Network Management Card – User Manual 34003991EN/EB Page 82/118...
  • Page 83 Set the SA1 switches to select the two wires configuration with termination: The next figure gives a typical bus structure in the two wires configuration: Network Management Card – User Manual 34003991EN/EB Page 83/118...
  • Page 84: Rs485 Link Configuration For 4 Wires Connexion

    7.2.2.3 RS485 link configuration for 4 wires connexion Set the SA2 switches like below: Set the SA1 switches to select the four wires configuration with no termination: Network Management Card – User Manual 34003991EN/EB Page 84/118...
  • Page 85 Set the SA1 switches to select the four wires configuration with termination: The next figure gives a typical bus structure in the four wires configuration: Network Management Card – User Manual 34003991EN/EB Page 85/118...
  • Page 86: Configuration Of The Jbus/Modbus Communication Parameters

    Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop bit, and without flow control. Check that UPS power is on. Enter the admin password (not modifiable). Network Management Card – User Manual 34003991EN/EB Page 86/118...
  • Page 87 Slave number : 7 Speed : 9600 bds Data : 8 bits stop bit : 1 Parity : None 7.2.3.2 Choice 2: Modify Jbus settings Enables the modification of Jbus settings. Network Management Card – User Manual 34003991EN/EB Page 87/118...
  • Page 88 7.2.3.5 Choice 5: Return to Jbus Default Configuration Returns to the Jbus default configuration (0x01, 9600, 8, 1, none) Wait during Jbus configuration returns to default ... Jbus Configuration has been set to default one. Network Management Card – User Manual 34003991EN/EB Page 88/118...
  • Page 89 Send : 01 81 02 c1 91 Recv : 01 03 00 62 00 64 e5 ff Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ... Network Management Card – User Manual 34003991EN/EB Page 89/118...
  • Page 90: A Dditional W Eb

    7.3 Additional Web pages The INMC card Jbus parameters could be set through the next page: Network Management Card – User Manual 34003991EN/EB Page 90/118...
  • Page 91: Jbus Table

    Charger general fault Battery charge Converter fault Inverter fault Network Management Card – User Manual Status to 0 Status to 1 Word (hex) absent present absent present absent present not in in charge charge 34003991EN/EB 1 & 3 Page 91/118...
  • Page 92 Output apparent power % output load level Power factor (Cos PHI) Mains 1 frequency Output frequency Battery backup time Battery charging level U mains 1 Nominal voltage of battery element Network Management Card – User Manual Word (hex) Unit 34003991EN/EB Page 92/118...
  • Page 93: Data For Pulsar M 2200 / 3000

    Phase M2 out of tolerance Charger general fault Battery charge Converter fault Inverter major fault Network Management Card – User Manual Status to 0 Status to 1 absent present absent present open closed absent present 34003991EN/EB Word (hex) 1 & 3 Page 93/118...
  • Page 94 Output apparent power % output load level Power factor x 100 Mains 1 frequency Output frequency Battery backup time Battery charging level U mains 1 Nominal voltage of battery element Network Management Card – User Manual Word (hex) 34003991EN/EB Unit Page 94/118...
  • Page 95: Data For Pulsar Mx 4000 / 5000 / 10000 And Ex 5 / 7 / 11 Rt

    Inverter thermal overload Inverter limitation UPS fuse fault Network Management Card – User Manual Status to 0 Status to 1 Word (hex) absent present absent present open closed absent present absent present absent present 34003991EN/EB 1 & 3 Page 95/118...
  • Page 96 % output load level Power factor (Cos PHI) Mains 1 frequency Mains 2 frequency Output frequency Battery backup time Battery charging level U mains 1 Nominal voltage of battery element Network Management Card – User Manual Word (hex) Unit 34003991EN/EB Page 96/118...
  • Page 97: Data For Pulsar Mx Frame 15 / 20

    Inverter thermal overload Inverter limitation UPS fuse fault Network Management Card – User Manual Status to 0 Status to 1 Word (hex) absent present absent present open closed absent present absent present absent present 34003991EN/EB 1 & 3 Page 97/118...
  • Page 98 Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present 34003991EN/EB Word (hex) Page 98/118...
  • Page 99 Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present Absent Present 34003991EN/EB Word (hex) Page 99/118...
  • Page 100 Peak factor phase 2 x 100 Peak factor phase 3 x 100 Power factor x 100 Mains 1 frequency Mains 2 frequency Output frequency Battery backup time Battery charging level Network Management Card – User Manual Word (hex) Unit 34003991EN/EB Page 100/118...
  • Page 101 Description of the physical quantity U mains 1 (phase 1) U mains 1 (phase 2) U mains 1 (phase 3) Nominal voltage of battery element Network Management Card – User Manual Word (hex) Unit 34003991EN/EB Page 101/118...
  • Page 102: Sensor Data

    Alarm : humidity too high Alarm : temperature too low Alarm : temperature too high Communication fault Input 1 Input 2 Network Management Card – User Manual Status to 0 Status to 1 open close open close 34003991EN/EB Word (hex) Page 102/118...
  • Page 103 Input 2 changing date (MSB) in Unix timestamp Input 2 changing date (LSB) in Unix timestamp Network Management Card – User Manual Word (hex) 34003991EN/EB Unit ° C / ° F ° C / ° F ° C / ° F...
  • Page 104 Inputs call mask – input 2 open notification Inputs call mask – low temperature notification Inputs call mask – high temperature notification Input 1 identification Input 2 identification Network Management Card – User Manual Word (hex) 34003991EN/EB Unit Page 104/118...
  • Page 105: Other Data

    7.4.6 Other data Information description Manufacturer name Product name UPS model Serial number Network Management Card – User Manual Word (hex) Example « MGE Office Protection Systems » « Pulsar » « 700 » « AN2E49008 » 34003991EN/EB Page 105/118...
  • Page 106: Appendices

    Battery switch (QF1) closed Manual Bypass switch (Q3BP) open Output switch (Q5N) closed Load OK Negative DC bus OK Positive DC bus OK Negative DC bus OK Positive DC bus OK Inverter end of limitation Input fuses OK Inverter OK 34003991EN/EB Page 106/118...
  • Page 107 L'humidité est en dessous du seuil bas xx % <Sensor name>: <Input #1 label> <when closed label> <Sensor name>: <Input #1 label> <when open label> <Sensor name>: <Input #2 label> <when closed label> <Sensor name>: <Input #2 label> <when open label> 34003991EN/EB Page 107/118...
  • Page 108 Load protected - Return from Bypass Battery switch (QF1) closed Manual Bypass switch (Q3BP) open Inverter end of limitation Inverter load OK Inverter temperature OK Inverter load OK Negative DC bus OK Positive DC bus OK Negative DC bus OK 34003991EN/EB Page 108/118...
  • Page 109: Table Of Ups Events

    Automatic Bypass temperature OK Bypass AC phase OK Automatic Bypass load OK Load protected - Return from Bypass Bypass AC voltage OK Battery switch (QF1) closed Manual Bypass switch (Q3BP) open Inverter end of limitation Input fuses OK 34003991EN/EB Page 109/118...
  • Page 110 UPS temperature OK UPS OK <Sensor Name> : Temperature is in normal range <Sensor Name> : Temperature is in normal range <Sensor Name> : Temperature is in normal range <Sensor Name> : Temperature is in normal range 34003991EN/EB Page 110/118...
  • Page 111: Table Of System Alarms

    Connected NSM list Full, last connection refused sendTrap()-> Unable to resolve hostname <hostname> SNMP Send Trap # <num> failure to <hostname> Time changed by user with yyyy/mm/dd hh:mm:ss Time synchronized by NSM or EPM with yyyy/mm/dd hh:mm:ss Network Management Card – User Manual 34003991EN/EB Page 111/118...
  • Page 112: Snmp Objects

    1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) DeciVolts DeciVolts DeciVolts DeciHz DeciHz DeciHz DeciAmps DeciAmps DeciAmps deciVolts deciVolts deciVolts 34003991EN/EB Download. Add.path {1,1,0} {1,2,0} {1,4,0} {1,7,0} {4,7,0} {4,8,0} {4,9,0} {4,12,0} {5,1,0} {5,2,0} {5,5,0} {5,6,0} {5,9,0} {5,11,0} {5,14,0}...
  • Page 113 Network Management Card – User Manual deciHz deciHz deciHz deciAmps deciAmps deciAmps 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 1(yes) 2(no) 34003991EN/EB {7,2,1,3,1,0} {7,2,1,3,2,0} {7,2,1,3,3,0} {7,2,1,4,1,0} {7,2,1,4,2,0} {7,2,1,4,3,0} {7,2,1,5,1,0} {7,2,1,5,2,0} {7,2,1,5,3,0} {7,3,0} {7,4,0} {7,7,0} {7,9,0} {7,10,0}...
  • Page 114 Network Management Card – User Manual 0.1 degré 0.1 % 1(yes) 2(no) 0.1 degré 1(yes) 2(no) 1(yes) 2(no) 0.1 % 1(yes) 2(no) 1(yes) 2(no) closed(1), open(2) closed(1), open(2) 34003991EN/EB {8,1,0} {8,2,0} {8,6,0} {8,7,1,1,1 } {8,7,1,2,1} {8,7,1,3,1} {8,7,1,4,1} {8,7,1,5,1} {8,7,1,6,1} {8,7,1,7,1} {8,7,1,8,1} {8,7,1,9,1}...
  • Page 115: Table Des Traps : (1.3.6.1.4.1.705.1.11)

    Level 2 Trap 53 Level 2 Trap 54 Level 2 Trap 55 Level 2 Trap 56 Level 2 Trap 57 Level 2 Trap 58 Level 2 Trap 59 Level 2 Trap 60 Level 2 Trap 61 Level 2 34003991EN/EB Page 115/118...
  • Page 116 The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page Network Management Card – User Manual Trap 62 Level 2 Trap 64 Level 2 Trap 63 Level 2 34003991EN/EB Page 116/118...
  • Page 117: Glossary

    Communication cards to supervise UPS and communicate with Network Shutdown Module to insure power protection on servers NETWORK MANAGEMENT PROXY Communication software installed on a PC connected to the UPS to supervise it and communicate with Network Shutdown Module to insure power protection on servers Network Management Card – User Manual 34003991EN/EB Page 117/118...
  • Page 118 Trap (SNMP) : This term describes an event that affects an MIB variable. Traps are sent to the manager, which is programmed to perform specific tasks upon reception of the traps. Network Management Card – User Manual 34003991EN/EB Page 118/118...

This manual is also suitable for:

66102

Table of Contents