Chassis Clearances
Figure A-15
4
1
Cisco Nexus 7004 chassis
2
Cable management frames
3
Vertical rack-mount posts
4
Vertical rack-mount posts for neighboring
racks
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
A-24
Clearances Required for the Cisco Nexus 7004 in a Two-Post Rack with Front-Mount
Brackets
8
9
17.3 in
(43.9 cm)
7
1
3
3
2
5
10
11
12
4
13
6
14
8
No left side clearance required (no airflow on
left side)
9
Chassis width.
10 Right side clearance recommended for open
rack installations:
If next to another open rack, use 6 inches
(15.2 cm) between racks.
If next to a wall, use 11 inches (27.9 cm)
between the chassis and the wall.
11 No rear clearance required but the rear must
be open to the hot aisle to exhaust air
Appendix A
Technical Specifications
OL-23069-07