Replacing the Front Door and Air Intake Assemblies on the Cisco Nexus 7018 Chassis
Figure 10-48
Positioning the Air Intake Frame on the Chassis
1
Fasten the captive screws on the air intake frame to the chassis and tighten to 11 to 15 in-lb (95 to
Step 11
130 N·m).
On the chassis door, pull the door handle open on one of the two sides of the door until the handle clicks
Step 12
(the handle clicks when you pull it out about 30 degrees).
Move the side of the door with the opened handle onto the two hinge pins as shown in
Step 13
Make sure that the hinge pins on the top cover and bottom hinge bracket fit through the slots on the top
and bottom of that side of the door. Position the door so the hinge pins are located at the ends of the slots.
The double-hinged door can be installed and opened on either side. The figures in this procedure show
Note
how to install the door on the left side first, but you can use the instructions to install it on either side first.
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
10-96
Ball-point studs
Chapter 10
Installing or Replacing Components
2
Air-intake frame with holes to be aligned with
the ball-point studs
Figure
10-49.
OL-23069-07