Cisco Nexus 7000 Hardware Installation And Reference Manual page 149

7000 series
Hide thumbs Also See for Nexus 7000:
Table of Contents

Advertisement

Chapter 5
Installing a Cisco Nexus 7018 Chassis
Figure 5-18
Positioning the Air Intake Frame on the Chassis
1
Fasten the captive screws on the air-intake frame to the chassis and tighten to 11 to 15 in-lb (95 to
Step 9
130 N·m).
On the chassis door, pull the door handle open on one of the two sides of the door until the handle clicks
Step 10
(the handle clicks when you pull it about 30 degrees).
Move the side of the door with the opened handle onto the two hinge pins as shown in
Step 11
sure that the top and bottom hinge pins on the hood and hinge bracket fit through the slots on the top and
bottom of that side of the door. Position the door so that the hinge pins are located at the ends of the slots.
The double-hinge door can be installed and opened on either side. The figures in this procedure show
Note
how to install the door on the left side first, but you can use the instructions to install it on either side.
OL-23069-07
Ball-headed studs
2
Air-intake frame with holes to be aligned with
the ball-headed studs
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Installing the Front Door and Air Intake Frame
Figure
5-19. Make
5-27