Grounding The Cisco Nexus 7010 Chassis - Cisco Nexus 7000 Hardware Installation And Reference Manual

7000 series
Hide thumbs Also See for Nexus 7000:
Table of Contents

Advertisement

Chapter 4
Installing a Cisco Nexus 7010 Chassis
Figure 4-4
1

Grounding the Cisco Nexus 7010 Chassis

The Cisco Nexus 7010 system is grounded through the AC power supply cables and one of two
grounding connections on the chassis. The AC power supply cables provide a connection to an earth
ground whenever you connect the AC power to the system. The system ground, also referred to as the
network equipment building system (NEBS) ground, provides additional grounding for EMI shielding
requirements and for the low-voltage supplies (DC-DC converters) on the modules. This grounding
system is active even when the AC power cables are not connected to the system. You establish this
ground by connecting one of the two grounding pads on the chassis to the rack (if it is connected to an
earth ground) or directly to the earth ground for the data center building.
This section includes the following topics:
OL-23069-07
Attaching the Cisco Nexus 7010 Chassis to the Rack
Handles used to adjust the chassis placement 2
Prerequisites for Grounding the Chassis, page 4-12
Required Tools and Equipment, page 4-12
Connecting the System Ground, page 4-12
Four M6 x 19 mm or 10-24 x 3/4 in. Phillips
screws used to attach each side bracket to a
front mounting rail (use a total of eight
screws)
Cisco Nexus 7000 Series Hardware Installation and Reference Guide

Grounding the Cisco Nexus 7010 Chassis

4-11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 7004Nexus 7009Nexus 7010Nexus 7018

Table of Contents