Installing the Front Door and Air Intake Frame
To install the front door and air intake frame to the Cisco Nexus 7018 cable management system, follow
these steps:
Position the left door stopper (700-27454-01) on the middle of the left cable management frame and
Step 1
fasten it with two M3x10 pan-head screws as shown in
in-lb (0.6 to 0.8 N·m).
Figure 5-13
1
Left door stopper identified with an L on the
bottom of the base.
2
Two M3x10 screws that fasten the stopper to
the cable management frame.
Position the right door stopper (700-27592-01) on the middle of the right side of the cable management
Step 2
frame and fasten it with two M3x10 pan-head screws as shown in
to 5 to 7 in-lb (0.6 to 0.8 N·m).
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
5-22
Attaching the Left Door Stopper
Chapter 5
Installing a Cisco Nexus 7018 Chassis
Figure
5-13. Tighten these two screws to 5 to 7
3
Screw holes on the cable management frame.
Figure
5-14. Tighten these two screws
OL-23069-07