Cisco Nexus 7000 Hardware Installation And Reference Manual page 111

7000 series
Hide thumbs Also See for Nexus 7000:
Table of Contents

Advertisement

Chapter 4
Installing a Cisco Nexus 7010 Chassis
Figure 4-5
1
NRTL listed 45-degree grounding lug
Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely
Step 3
attached to the ground lug by attempting to pull the wire out of the crimped lug.
Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire
Step 4
lug to the grounding pad with two M4 screws.
the front side of the chassis.
grounding lug and the grounding wire do not interfere with other switch hardware or rack equipment.
Figure 4-6
1
Grounding pad
OL-23069-07
Inserting the Grounding Wire in the Grounding Lug
Figure 4-7
shows the location on the rear of the chassis. Ensure that the
Grounding Pad on the Front of the Cisco Nexus 7010 Chassis
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Grounding the Cisco Nexus 7010 Chassis
2
Grounding cable with 0.75 in. (19 mm) of insulation
stripped from the end
Figure 4-6
shows the location of the grounding pads on
4-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 7004Nexus 7009Nexus 7010Nexus 7018

Table of Contents