Infeed
1.1 Active Infeed
1.1.2

Active Infeed closed-loop control Booksize

Schematic structure
Figure 1-1
Active Infeed closed-loop control for Active Line Modules Booksize
The Active Line Module can be operated in two different modes depending on the
parameterized line supply voltage (p0210):
● Active Mode
● Smart Mode
The DC link voltage setpoint (p3510) and the control type are preset as follows during
commissioning in line with the connection voltage (p0210):
Table 1-1
Presetting the control type and DC link voltage booksize
Supply voltage p0210 [V]
Control type p3400.0
Vdc_soll p3510 [V]
22
Schematic structure of Active Infeed Booksize
In Active Mode, the DC link voltage is regulated to a variable setpoint (p3510), which
results in a sinusoidal line current (cosφ = 1). The level of the reactive current is also
controlled and can be specifically defined.
Energy recovery capability is maintained in Smart Mode, although there is a lower DC link
voltage in comparison to the Active Mode. The DC link voltage is dependent on the
current line voltage.
380-400
600
401-415
"0" = Active Mode
625
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
416-440
460
"1" = Smart Mode
562-594
621
1)
1)
480
648
1)
Drive Functions