Siemens SINAMICS S120 Function Manual page 501

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

The component has been successfully replaced
Example: Replacing a Motor Module/Power Module with a different power rating
Precondition:
The replaced power unit has a different power rating
Vector: Power rating of the Motor Module/Power Module not greater than 4 * motor current
Table 12-13 Example: Replacing a power unit with a different power rating
The component has been successfully replaced
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Action
Set p9905 to "1"
Action
Switch off the power supply
Replace the defective
component and connect the
new one
Switch on the power supply
Drive Object CU:
p0009 = 1
p9906 = 2
p0009 = 0
p0977 = 1
Drive Object component:
p0201 = r0200
p0010 = 0
p0971 = 1
Basic information about the drive system
12.7 Examples of replacing components
Reaction
Alarm disappears
The serial number is copied
to the target topology
Reaction
Alarm A01420
Device configuration
Component comparison
Completing the configuration
Data Backup
Use the code number
Completing commissioning
Data Backup
Comments
The serial number is stored in
the RAM of the Control Unit and
has to be copied to the non-
volatile memory with p0971 or
p0977.
Comments
For p9906=2: Caution
Topology monitoring for all
(!) components heavily
reduced so that DRIVE-CLiQ
lines may be hidden by
mistake.
The new order number is
stored in the RAM of the
Control Unit and has to be
copied to the non-volatile
memory with p0971 or
p0977.
501