Siemens SINAMICS S120 Function Manual page 367

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Bit
Meaning
12
Holding brake open
13
No motor overtemperature alarm
14
n_act >= 0
15
Alarm, drive converter thermal
overload
STW1 (status word 1), positioning mode, p0108.4 = 1
See function diagram [2479]
Table 10-12 Description of STW1 (status word 1, positioning mode)
Bit
Meaning
0
Ready to power-up
1
Ready to run
2
Operation enabled
3
Fault active
4
Coasting active (OFF2)
5
Fast stop active (OFF3)
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Comments
1
Holding brake open
0
Holding brake closed
1
Motor overtemperature alarm not active
0
Motor overtemperature alarm active
1
Actual speed > = 0
0
Actual speed < 0
1
No alarm present
0
Alarm, converter thermal overload
The overtemperature alarm for the converter is
active.
Comments
1
Ready to start
Power supply on, electronics initialized, line
contactor released if necessary, pulses inhibited.
0
Not ready to start
1
Ready to operate
Voltage at Line Module (i.e. line contactor closed (if
used)), field being built up.
0
Not ready to operate
Reason: No ON command has been issued.
1
Operation enabled
Enable electronics and pulses, then ramp up to
active setpoint.
0
Operation inhibited
1
Fault active
The drive is faulty and, therefore, out of service.
The drive switches to Power-on inhibit once the
fault has been acknowledged and the cause has
been remedied.
The active faults are stored in the fault buffer.
0
No fault present
No active fault in the fault buffer.
1
No OFF2 active
0
Coasting active (OFF2)
An OFF2 command is present.
1
No OFF3 active
0
Fast stop active (OFF3)
An OFF3 command is present.
Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
BICO
BO: r0899.12
BO: r2135.14
(inverted)
BO: r2197.3
BO: r2135.15
(inverted)
BICO
BO: r0899.0
BO: r0899.1
BO: r0899.2
BO: r2193.3
BO: r0899.4
BO: r0899.5