11.3 Motor changeover
● 4 drive data sets (DDS), p0180 = 4
● 4 digital outputs to control the auxiliary contactors
● 4 digital inputs to monitor the auxiliary contactors
● 2 digital inputs for selecting the data set
● 4 auxiliary contactors with auxiliary contacts (1 NO contact)
● 4 motor contactors with positively-driven auxiliary contacts (3 NC contact, 1NO contact)
● 4 motors, 1 Control Unit, 1 infeed, and 1 Motor Module
Figure 11-2
Table 11-3
p0130
p0180
p0186[0..3]
p0820, p0821
p0822 to p0824
p0826[0..3]
p0827[0..3]
p0830.1 to
p0830.4
p0831[0..3]
456
Example of motor changeover
Settings for the example
Parameter
Settings
4
4
0, 1, 2, 3
Digital inputs DDS
selection
0
1, 2, 3, 4
1, 2, 3, 4
Digital outputs, auxiliary
contactors
Digital inputs, auxiliary
contacts
Configure 4 MDS
Configure 4 DDS
The MDS are assigned to the DDS.
The digital inputs for motor switchover via DDS
selection are selected. Binary coding is used
(p0820 = bit 0 etc.).
Different numbers indicate a different thermal model
The bits of p0830 are assigned to the MDS. If
p0827[0] = 1, for example, bit p0830.1 is set when
MDS0 is selected via DDS0.
The digital outputs for the auxiliary contactors are
assigned to the bits.
The digital inputs for the feedback signal of the motor
contactors are assigned.
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Remark
Drive Functions