Instructions For Offline Commissioning With Starter - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Applications
11.4 Application examples with the DMC20
Note
Drives with enabled safety functions must not be deactivated, see chapter "Safety
Integrated" for further details.
Figure 11-5
Note
In order to disconnect and isolate the power unit from the DC link, additional measures must
be applied - such as DC link wiring through the DC link infeed adapter and DC link
disconnecting devices. The safety information and instructions in the Equipment Manual
must be carefully observed.
11.4.5

Instructions for offline commissioning with STARTER

With automatic online configuration in STARTER, the DMC20 is detected and adopted in the
topology. Offline commissioning requires the following operation steps:
1. Configure a drive unit offline
2. Right-click on Topology -> enter new object -> DRIVE-CLiQ Hub
3. Configuring a topology
462
Example: topology vector V/f hot plugging
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4