Siemens SINAMICS S120 Function Manual page 83

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 3-7
Example of general 2nd order filter
STARTER filter parameters
Numerator frequency f
Z
Numerator damping D
Z
Denominator frequency f
Denominator damping D
Parameterization
The "current setpoint filter" parameter screen is selected via the following icon in the toolbar
of the STARTER commissioning tool:
Figure 3-13
Function diagrams (see SINAMICS S List Manual)
● 5710 Current setpoint filters
Overview of key parameters (see SINAMICS S List Manual)
● p1656 Activates current setpoint filter
● p1657 Current setpoint filter 1 type
● p1658 Current setpoint filter 1 denominator natural frequency
● p1659 Current setpoint filter 1 denominator damping
● p1660 Current setpoint filter 1 numerator natural frequency
● p1661Current setpoint filter 1 numerator damping
● ...
● p1676 Current setpoint filter 4 numerator damping
● p1699 Filter data transfer
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Amplitude log frequency curve
= 500 Hz
= 0.02 dB
= 900 Hz
N
= 0.15 dB
N
STARTER icon for "current setpoint filter"
Servo control
3.7 Current setpoint filter
Phase frequency curve
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents