Setting Power Supply
Status
Setting External Alarm
Status
To display the Shelf Configuration menu, select [0] Shelf from the List Card menu.
Figure 82 Shelf Configuration Menu
The Shelf Configuration menu displays the following information about the shelf:
Hardware revision
n
Serial number
n
Power supply status (in service or out of service) for power supplies 1-6
n
External alarm status (normally open or normally closed) for external alarms 1-3
n
To set the status of a power supply, follow these steps:
1 From the List Card menu, shown earlier in Figure 81, select [0] Shelf to open the
Shelf Configuration menu, shown earlier in Figure 82.
2 Enter the number corresponding to the power supply that you want to set. The
following prompt appears:
Enter Power Supply (1= Out of Service, 2= In Service):
3 Enter 1 to take the power supply out of service or 2 to put the power supply
into service.
The PathBuilder S700 supports up to three alarms from outside equipment. To set
the external alarms, follow these steps:
1 From the List Card menu, shown earlier in Figure 81, select [0] Shelf to open the
Shelf Configuration menu, shown earlier in Figure 82.
2 Enter the number corresponding to the external alarm that you want to set (7 for
alarm #1, 8 for alarm #2, or 9 for alarm #3).
The following prompt appears:
Enter External Alarm 1 (1= Normally Open, 2= Normally Closed)
3 Enter 1 to set the alarm to normally open or 2 to set the alarm to normally closed.
For details about how to connect the external alarms, see "Connecting the Office
Alarms" in Chapter 2.
Configuring the Shelf
121