HP ProLiant DL560 Gen11 User Manual page 132

Advertisement

If you are installing the HPE Smart Storage Hybrid Capacitor, verify that the system meets the minimum firmware requirements .
Procedure
Procedure
1. Power down the server.
2. If installed, open the cable management arm .
3. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4. Disconnect all peripheral cables from the server.
5. Remove the server from the rack .
6. Place the server on a flat, level work surface.
7. Remove the access panel .
8. Do one of the following:
Remove the air baffle .
Remove the processor mezzanine tray .
9. Remove the fan cage.
10. Install the energy pack:
a. Insert the energy pack at an angle (callout 1).
b. Pivot the energy pack downward (callout 2).
Make sure that the energy pack is locked in the retention latch.
c. Connect the energy pack cable (callout 3).
11. Connect the storage backup power cable .
12. Install the fan cage.
HPE ProLiant DL560 Gen11 Server User Guide
132