Goodrive270 series VFD for fan and pump
Related parameter list:
Function
code
HVAC function
P94.00
Variable-frequency
P94.10
motor run mode
Total number of
P94.11
P26.06
P26.07
P26.08
P26.09
Name
0: Invalid
selection
1: Valid
0: Fixed
1: Circular
0–8: Corresponding to motors
A–H. The sequence numbers
motors
must be successive.
RO5 output
0–47: Same as those for standard
models
RO6 output
48: Fire mode activated
RO7 output
49: Pre-alarm of PID1 feedback
too low
50: Pre-alarm of PID1 feedback
too high
51: VFD in sleep
52: PID2 in running
53: PID2 stop
54: Indication of run with backup
pressure
55: Water shortage indication of
inlet pool
56: Pre-alarm
57: Control variable-frequency
RO8 output
circulation pump A
58: Control variable-frequency
circulation pump B
59: Control variable-frequency
circulation pump C
60: Control variable-frequency
circulation pump D
61: Control variable-frequency
circulation motor E
62: Control variable-frequency
circulation motor F
63: Control variable-frequency
circulation motor G
Description
-135-
Basic operation guidelines
Value
Modify
◎
1
◎
1
◎
4
○
57
○
58
○
59
○
60
Need help?
Do you have a question about the Goodrive270 Series and is the answer not in the manual?