Goodrive270 series VFD for fan and pump
Function
Name
code
Motor stalling
P96.28
function selection
P96.29 Stalling current limit
Stalling frequency
P96.30
upper limit
Stalling detection
P96.31
time
Motor dry pumping
P96.32
function selection
Current limit for
P96.33
motor dry pumping
Detection time for
P96.34
motor dry pumping
Motor
P96.35
overtemperature
point
Description
Prerequisite for selecting the function: The VFD
exceeds the stalling current limit, the output
frequency is lower than the stalling frequency
upper limit, and the duration of this situation
exceeds the stalling time.
0: Disable
1: Alarm
2: Faulty
0.0–1600.0%
Note: 100.0% corresponds to the motor rated
current.
0.00–P00.06
It cannot be lower than 10Hz.
0.0–3600.0s
0: Disable
1: Alarm
2: Faulty
0.0%–100.0%
Note: 100.0% corresponds to the motor rated
current.
0.0–3600.0s
When the detected motor temperature is higher
than the value of this function code, a fault is
reported.
-265-
Function parameter list
Default Modify
○
0
○
200.0%
○
15Hz
○
2.0s
○
0
○
0.0%
○
2.0s
110.0°