Goodrive270 series VFD for fan and pump
Function
Name
code
Setting source of
P03.19
braking torque
upper limit
Electromotive
P03.20
torque upper limit
set through keypad
Braking torque
P03.21
upper limit set
through keypad
Weakening
coefficient in
P03.22
constant power
zone
Lowest weakening
P03.23
point in constant
power zone
Description
7: Ethernet communication
8: Reserved
9: PROFINET communication
10–17: Reserved
18: Keypad (for small power models)
0: Keypad (P03.21)
1: AI1 (100% corresponding to triple the motor
rated current)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA
5: Modbus communication
6: PROFIBUS/CANopen communication
7: Ethernet communication
8: Reserved
9: PROFINET communication
10–17: Reserved
18: Keypad (for small power models)
Used to set torque limits.
Setting range: 0.0–300.0% (of the motor rated
current)
Used when the AM is in flux-weakening control.
T
Min. flux-weakening limit of motor
The function codes P03.22 and P03.23 are valid
at constant power. The motor enters the
flux-weakening state when the motor runs above
the rated speed. Change the flux-weakening
curvature by modifying the flux-weakening
-168-
Flux-weakening
coefficient of motor
0.1
1.0
2.0
f
Function parameter list
Default Modify
0
180.0%
180.0%
0.3
20%