To remove and replace the filters:
a.
Remove one top screw and two bottom screws securing each UPM front panel (see
each panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b.
Remove one top screw and two bottom screws securing the ISBM left front panel (see
the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
c.
If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the door
open (see
d.
Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from
the cabinet.
e.
Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seated
against the cabinet.
f.
Reinstall the UPM section front panels removed in Step a and secure with the retained hardware.
g.
Reinstall the ISBM section front panel removed in Step b and secure with the retained hardware.
h.
If opened, close the front door and secure the latch.
Figure 113. ISBM Section Air Filter Locations – Continuous Static Switch
ISBM Section
Air Filters
Figure
13).
Eaton
®
Power Xpert
®
9395P-600 Installation and Operation Manual 164000562—Rev 08
UPS Maintenance
UPM Section
Air Filters
Figure
13). Lift
Figure
13). Lift
179