Omron OMNUC R88D-WT15HF User Manual page 321

Table of Contents

Advertisement

Operation
Note 2. This new parameter is supported by Servo Drivers with software version "r.0037."
H Position Control Parameters (From Pn200)
D Position Control Setting 1 (Pn200: Default Setting 1011)
Pn200.0
Position control setting 1 –– Command pulse mode (Position)
Setting
0 to 9
range
Note Refer to 4-4-3 Important Parameters for details.
Pn200.1
Position control setting 1 –– Deviation counter reset (Position)
Setting
0 to 3
range
Setting Explanation
Setting
0
Reset deviation counter using high level signal (status signal)
1
Reset deviation counter using rising signal (Low to High)
2
Reset deviation counter using low level signal (status signal)
3
Reset deviation counter using sinking signal (High to Low)
• Sets input conditions under which ECRST (deviation counter reset input, CN1-15: +ECRST, CN1-14:
–ECRST) is enabled.
• If using an OMRON Position Control Unit, do not change the default setting.
Pn200.2
Position control setting 1 –– Deviation counter reset when servo is OFF and an alarm occurs
(Position)
Setting
0 to 2
range
Setting Explanation
Setting
0
Reset deviation counter when servo is OFF and an alarm occurs
1
Do not reset deviation counter when servo is OFF and an alarm occurs
2
Reset deviation counter if alarm occurs, regardless of servo status
• Sets whether the deviation counter will be reset when the servo is OFF and an alarm occurs.
• If the deviation counter is not reset (setting 1 or 2), the next time the servo is turned ON, the Servomo-
tor will rotate only to the number of deviation counter residual pulses. Be careful, because the servo
begins to operate as soon as the power is turned ON.
Pn200.3
Position control setting 1 –– Pulse command filter selection
Setting
0, 1
range
Setting Explanation
Setting
0
Command filter for line driver signal input (500 kpps)
1
Command filter for open collector signal input (200 kpps)
4-58
Unit
---
Unit
---
Unit
---
Unit
---
Default
1
setting
Default
1
setting
Explanation
Default
0
setting
Explanation
Default
1
setting
Explanation
Chapter 4
Restart
Yes
power?
Restart
Yes
power?
Restart
Yes
power?
Restart
Yes
power?