Residual Current Preprocessing, Current Measured As Voltage Resutctr - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
3.17.4
Residual current preprocessing, current measured as
voltage RESUTCTR
3.17.4.1
Identification
Function description
Residual current preprocessing, cur-
rent measured as voltage
3.17.4.2
Function block
Figure 93: Function block
3.17.4.3
Functionality
The preprocessing block RESUTCTR is used for setting up the residual current
measurement when the current is measured as voltage and the measured signal
is wired via VT channel.
Input channel for RESUTCTR can be physical hardware voltage channel only.
The output
GSLPTOC which optionally can use this special way of current measurement.
The residual primary rated current can be set using
The setting
arrangement. This is used as a reference to scale the measurements accordingly.
Residual current magnitude correction of an external measuring arrangement can
be made using
Residual current angle correction of an external measuring arrangement can be
made using
Reverse polarity setting is used to reverse the polarity of residual CT.
Purpose of the outputs IRES_MEAS and IRES_MEAS_DR are described in the
Outputs table.
Frequency adaptivity functionality is enabled by first enabling the main
adaptivity setting under System parameter settings (Configuration > System >
Frequency adaptivity), then by setting RESUTCTR
"Enable".
REX640
Technical Manual
IRES_MEAS channel of the RESUTCTR can be connected to only
Secondary voltage defines the nominal voltage of the measuring
Amplitude Corr setting.
Angle Correction setting.
IEC 61850
IEC 60617
identification
identification
RESUTCTR
Io(U)
Primary current setting.
Frequency adaptivity mode to
Basic functions
ANSI/IEEE
identification
Io(U)
Frequency
203