The function contains a blocking functionality. It is possible to block function
outputs, timers or the function itself.
4.1.1.4
Analog input configuration
PHxPTOC has one analog group input which must be properly configured.
Table 362: Analog inputs
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.1.1.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of PHxPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
ENA_MULT
Figure 198: Functional module diagram
Level detector
The measured phase currents are compared phasewise to the set
measured value exceeds the set
of the value to the phase selection logic. If the ENA_MULT input is active, the
value setting is multiplied by the Start value Mult setting.
REX640
Technical Manual
See the preprocessing function blocks in this document for the possible
signal sources.
I_A
I_B
I3P
I_C
BLOCK
The protection relay does not accept the
setting if the product of these settings exceeds the
range.
Description
Three-phase currents
Phase
Level
selection
detector
logic
Blocking
logic
Start value , the level detector reports the exceeding
Protection functions
Operation setting. The
Timer
t
OPERATE
t
Start value . If the
Start value or Start value Mult
Start value setting
START
Start
327