SET EMU

Sets operating parameters for the environmental monitoring unit (EMU).
Syntax
SET EMU
Switches
The SENSOR and FANSPEED switches control both the master and slave EMU
settings. The EMU within the primary cabinet (master) instructs the EMUs within the
other cabinets to operate at the same SENSOR and FANSPEED settings to which the
master EMU is set.
SENSOR_1_SETPOINT=nn
SENSOR_2_SETPOINT=nn
SENSOR_3_SETPOINT=nn
SENSOR_x_SETPOINT=35 (Default)
Sets the acceptable temperatures (in Celsius) at which the subsystem operates. Sensor
1 and Sensor 2 set the maximum operating temperature for the primary subsystem
cabinet. Sensor 3 sets the maximum operating temperature for the EMU unit. The
allowable range for the setpoint is 0°C (32°F) to 49°C (120°F). The EMU determines
the default setpoint for all three sensors.
Table 5–7 lists the valid EMU set-point temperatures in both Fahrenheit and Celsius.