Alarm
Alarm Name
Sub
Number
Code
15
1031
MEMORY
0
ERROR(MOTION1
)
1
2
Meaning
Cause
YCP01 board failure (1)Turn the power OFF then back ON.
SVxS parameter error
Data error
YCP01 board failure (1)Turn the power OFF then back ON.
"GET FILE" instruction, "SET
Data error
FILE" instruction execution target
file
Home position calibration file
Data error
Tool file
Data error
Remedy
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
remove the CF from the failure YCP01 board to insert it into the new YCP01
board.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(2)If the alarm occurs again, replace the YCP01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YCP01 board, and then
remove the CF from the failure YCP01 board to insert it into the new YCP01
board.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.