Alarm
Alarm Name
Sub
Number
Code
54
55
56
Meaning
Cause
EAXA board failure
The system program of servo
Software operation
board #5 is damaged.
error occurred
EAXA board failure
The system program of servo
Software operation
board #6 is damaged.
error occurred
EAXA board failure
The system program of servo
Software operation
board #7 is damaged.
error occurred
EAXA board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.