Alarm History Clear; Rough Match Output; Software Limit - Mitsubishi Electric MELSERVO MR-J3-xT Instruction Manual

Servo amplifier
Table of Contents

Advertisement

6. PARAMETERS

6.3.4 Alarm history clear

The alarm history can be confirmed by using the MR Configurator. The servo amplifier stores one current
alarm and five past alarms from when its power is switched on first. To control alarms which will occur during
operation, clear the alarm history using parameter No. PC18 (alarm history clear) before starting operation.
Clearing the alarm history automatically returns to "
This parameter is made valid by switching power off, then on after setting.

6.3.5 Rough match output

Rough match (RXn2) is output when the command remaining distance reaches the value set in parameter No.
PC11 (rough match output range). The set remaining distance is 0 to 65535 [ 10
In position (RXnC)

6.3.6 Software limit

A limit stop using a software limit (parameter No. PC31 to PC34) is made as in stroke end operation. When a
motion goes beyond the setting range, the motor is stopped and servo-locked. This function is made valid at
power-on but made invalid during home position return. This function is made invalid when the software limit
setting is the same as the software limit
setting is less than the software limit
Parameter No. 16
0 0 0
Command remaining distance ( 10
set in parameter No. PC11
Servo motor
Command pulse
speed
Rough match
ON
OFF
(RXn2)
ON
OFF
setting. A parameter error (A37) will occur if the software limit
setting.
Inhibited area
Unmovable
Current position
0".
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
m)
STM
Actual servo motor speed
Movable area
Movable
Software limit
6 - 27
STM
m].