6. PARAMETERS
No.
Symbol
PB18
LPF
Low pass filter setting
Set the low pass filter.
Setting parameter No. PB23 (low pass filter selection) to "
automatically changes this parameter.
When parameter No. PB23 is set to "
manually.
PB19
VRF1
Vibration suppression control - vibration frequency setting
Set the vibration frequency for vibration suppression control to suppress low-
frequency machine vibration, such as enclosure vibration.
Setting parameter No. PB02 (vibration suppression control tuning mode) to "
1" automatically changes this parameter. When parameter No. PB02 is set
to "
PB20
VRF2
Vibration suppression control - resonance frequency setting
Set the resonance frequency for vibration suppression control to suppress low-
frequency machine vibration, such as enclosure vibration.
Setting parameter No. PB02 (vibration suppression control tuning mode) to "
1" automatically changes this parameter. When parameter No. PB02 is set
to "
PB21
For manufacturer setting
Do not change this value by any means.
PB22
PB23
VFBF
Low pass filter selection
Select the low pass filter.
0 0
When automatic setting has been selected, select the filter that has the band
width close to the one calculated with
PB24
*MVS
Slight vibration suppression control selection
Select the slight vibration suppression control.
When parameter No. PA08 (auto tuning mode) is set to "
parameter is made valid.
0 0 0
Name and Function
2", this parameter can be set manually.
2", this parameter can be set manually.
0
Low pass filter selection
0: Automatic setting
1: Manual setting (parameter No. PB18 setting)
VG2 10
1 + GD2
Slight vibration suppression control selection
0: Invalid
1: Valid
0
"
1
", this parameter can be set
[rad/s]
3", this
6 - 17
Setting
Initial Value
Unit
Range
3141
rad/s
18000
100.0
Hz
100.0
100.0
Hz
100.0
0.00
0.00
0000h
Refer to
Name and
function
column.
0000h
Refer to
Name and
function
column.
100
to
0.1
to
0.1
to