5. PARAMETERS
5.2.3

Using forward/reverse rotation stroke end to change the stopping pattern

The stopping pattern is factory-set to make a sudden stop when the forward/reverse rotation stroke end is
made valid. A slow stop can be made by changing the parameter No. 22 value.
Parameter No.22 Setting
0
(initial value)
1
5.2.4

Alarm history clear

The servo amplifier stores one current alarm and five past alarms from when its power is switched on first.
To control alarms which will occur during operation, clear the alarm history using parameter No.16 before
starting operation.
Sudden stop
Droop pulses are reset to make a stop.
Slow stop
Position control mode : The motor is decelerated to a stop in accordance with the
parameter No. 7 value.
Speed control mode
: The motor is decelerated to a stop in accordance with the
parameter No. 12 value.
Parameter No.16
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleard)
5 - 21
Stopping Method