Led Indicator - Advantech AMAX-5000 Series User Manual

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

5.2.1.2
Digital Input
Channels: 16
Digital Input:
Dry Contact:
Logic level 1: close to Iso.GND
Logic level 0: open
Wet Contact:
Rated voltage: 24V
Logic level 1: 10~30 V
Logic level 0: -3~3V
Input Delay:
From logic 0 to 1: 4ms
From logic 1 to 0: 4ms
Digital Filter: 3ms
Typical Input Current: Logic level 1: 1.3mA~4.3mA (10V~30V)
5.2.1.3
Protection
Isolation Voltage: 2,000V
5.2.1.4
Environment
Operation Temperature: -25~60°C (vertical mounted)
Storage Temperature: -40~85°C
Relative Humidity: 5~95% (non-condensing)
5.2.2

LED Indicator

Table 5.6: AMAX-5052Module LED Indicator
LED
Color
Power
Green
Green
Run
Green
DI0~7
Green
DI8~15
Yellow
AMAX-5000 Series User Manual
DC
and -10~-30V
DC
DC
DC
Figure 5.7 AMAX-5052 Module LED Indicator
Indication
ON
ON
Blink
ON
OFF
ON
OFF
78
DC
Behavior
Power on
EtherCAT connection
When TX/RX data in transmission
Dry/Wet Logic "1"
Dry/Wet Logic "0"
Dry/Wet Logic "1"
Dry/Wet Logic "0"

Advertisement