Advantech AMAX-5000 Series User Manual page 160

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

Pulse_Train_Pos_Width and Pulse_Train_Neg_Width:
The positive and negative level duration of the pulse output can be adjusted by these
two factors. If Pulse_Train_Pos_Width (0x8000:0B) is n, the positive level duration
will be n * 50 ns. The setting number should between 1~232.
For
example,
Pulse_Train_Neg_Width set to 2,000,0000.
Each output pulse will be: 50ms high and 100ms low.
Pulse_Train_Number:
The total number of pulse output can be set by Pulse_Train_Number (0x8000:0D),
the number should between 0~232 (0 is continues output).
6.2.8.7
Configuration Data (0xF600 - 0xFFFF)
Table 6.32: Configuration Data (0xF600 - 0xFFFF)
Index (hex)
Name
0xF600:01
LocateModule
Encoder Firm-
0xF600:09
ware Version
0xF600:0A
Alarm Status
F600:0A is System Alarm Status
0x00: Normal
0x01: Encoder FPGA is not Ready.(FPGA Firmware Version is 0x00 or 0xFF)
AMAX-5000 Series User Manual
if
Pulse_Train_Pos_Width
Meaning
Control LED
0: Disable
1: Enable
Encoder FPGA Firm-
ware Version
AMAX-5081 Alarm
status
148
set
to
1,000,000,
Data type Flags
Default value
BOOL
RW
0x00
BIT8
RO
0x00
BIT8
RO
0x00
the

Advertisement

Table of Contents
loading

Table of Contents