6.1.8.2
Output Data (0x7000 - 0x7FFF)
Table 6.11: Output Data (0x7000 - 0x7FFF)
Index (hex) Name
70n0:01
COn_Set_Counter
70n0:02
COn_Enable_Latch_Z
COn_En-
70n0:03
able_Latch_External
COn_Set_Counter_Val
70n0:11
ue
(n=0~1 for Ch0~1)
6.1.8.3
Configuration Data (0x8000 - 0x8FFF)
Table 6.12: Configuration Data (0x8000 - 0x8FFF)
Index (hex) Name
80n0:01
Cn_Mode_Select
Cn_Enable_Z_-
80n0:02
Pulse_Reset
Cn_Z_Pulse_Ac-
80n0:03
tive_Polarity
Cn_Enable_Exter-
80n0:04
nal_Reset
Cn_Exter-
80n0:05
nal_Latch_Ac-
tive_Polarity
Cn_Enable_Regis-
80n0:06
ter_Reload
Cn_Re-
80n0:07
load_Counter_Val-
ues
Cn_Input_Filter_-
80n0:08
Time
(n=0~1 for Ch0~1)
AMAX-5000 Series User Manual
Meaning
Data type
Set Counter
BOOL
Enable Z pin counter
BOOL
latching
Enable L pin counter
BOOL
latching
Set Counter Value
UDINT
Meaning
Select Encoder mode
0: Encoder mode
1: Bi-Direction Mode
Enable Z pulse input to
reset counter
0: Disable
1: Enable
The active polarity of Z
input
0: Rising Edge
1: Falling Edge
Enable external input to
reset counter
0: Disable
1: Enable
The active polarity of
Latch input
0: Rising Edge
1: Falling Edge
Enable the register
change of reload counter
0: Disable
1: Enable
Reload counter value
Input Filter Time
118
Flags
Default
RW
0x00
RW
0x00
RW
0x00
RW
0x00
Data type Flags
Default
UINT
RW
0x00
UINT
RW
0x00
UINT
RW
0x00
UINT
RW
0x00
UINT
RW
0x00
UINT
RW
0x00
0xFFFFF
UDINT
RW
FFF
0x00
UINT
RW
(Disable)