Advantech AMAX-5000 Series User Manual page 74

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

The actual display range for scaled data shows on the table below:
Table 4.47: Scaled Data Display Range
Item Name
+/-50 mV
+/-100 mV
+/-500 mV
+/-1 V
+/-2.5 V
K 0~1370°C
J 0~760°C
E 0~1000°C
T -100~400°C
R 500~1750°C
S 500~1750°C
B 500~1800°C
4.5.5.3
Configuration Data (0x8000 - 0x8FFF)
Table 4.48: Configuration Data (0x8000 - 0x8FFF)
Index (hex)
Name
80n0:01
AIn_EnBurnOut
80n0:11
AIn_Range
80n0:14
AIn_BurnOutValue
(n=0~5 for ch0~5)
AIn_EnBurnOut
When burnout detection is enabled, the limitation of conversion time per channel will
be 7.8ms. (21.4Hz for all channel)
Input Range Type
AMAX-5018 supporting voltage and thermocouple input range, like below:
Table 4.49: Input Range Type
Item Name
+/-50 mV
+/-100 mV
+/-500 mV
+/-1 V
+/-2.5 V
K 0~1370°C
J 0~760°C
E 0~1000°C
T -100~400°C
R 500~1750°C
S 500~1750°C
B 500~1800°C
AMAX-5000 Series User Manual
Scaled Data
-780000~780000
-1560000~1560000
-6250000~6250000
-12500~12500
-25000~25000
0~1370
0~7600
0~10000
-1000~4000
5000~17500
5000~17500
5000~18000
Meaning
Enable burnout
detection
Input range type
Burnout value
Value (UINT)
0x101
0x102
0x104
0x140
0x141
0x420
0x400
0x460
0x440
0x480
0x4A0
0x4C0
62
Physical Value
-78~78 mV
-156~156 mV
-625~625 mV
-1.25~1.25 V
-2.5~2.5 V
0~1370°C
0~760°C
0~1000°C
-100~400°C
500~1750°C
500~1750°C
500~1800°C
Data type Flags Default value
BOOL
RW
0x00 (Disable)
0x420 (K
UINT
RW
0~1370 °C)
UINT
RW
1 (Up Scale)

Advertisement