3.1.2.3
Digital Input
Channels: 4
Digital Input:
–
Wet Contact:
Rated voltage: 24V
Logic level 1: 10~30 V
Logic level 0: -3~3V
Input Delay:
–
From logic 0 to 1: 4ms
–
From logic 1 to 0: 4ms
Digital Filter: 3ms
3.1.2.4
Protection
Isolation Voltage: 2,000V
3.1.2.5
Environment
Operation Temperature: -10~60°C (vertical mounted)
Storage Temperature: -40~85°C
Relative Humidity: 5~95% (non-condense)
3.1.3
LED Indicator
Table 3.1: AMAX-5001 Module LED Indicator
LED
Color
PWR
Green
Run
Green
BUS
Green
OC
RED
OV1
RED
OV2
RED
UV1
RED
UV2
RED
AMAX-5000 Series User Manual
DC
and -10~-30V
DC
DC
DC
Figure 3.3 AMAX-5001 Module LED Indicator
Indication
ON
ON
ON
ON
ON
ON
ON
ON
12
DC
Behavior
Power on
EtherCAT connection
BUS power on
BUS over current
Vin1 over voltage (30V)
Vin2 over voltage (30V)
Vin1 under voltage (10.7V)
Vin2 under voltage(10.7V)