3.1.1

AMAX-5001 Application

The AMAX-5580 controller does not provide power to the right side EtherCAT bus,
due to power independent purpose, AMAX-5001 must be the first module on the right
side to provide independent power to the EtherCAT bus. In configuration with large
number of IO modules, it is possible to use another AMAX-5001 to provide the extra
2A power to the EtherCAT bus. It supplies power to the modules following on the
right side, and isolates them from the power on the left side. Please refer to the fol-
lowing diagram for the details.
3.1.2

AMAX-5001 Specification

3.1.2.1
General
Certification: CE, FCC class A
Connector: Pluggable 4P+8P push-in terminal (#24~16 AWG)
Enclosure: PC
Power Consumption: 2W @ 24V
Protocol: EtherCAT
Transmission Rate: 100Mbps
Distributed Clock: Default not supported
LED Indicator: PWR, RUN, Power Diagnosis LED
Weight: Approx. 80g
3.1.2.2
Power Input
Rated Voltage: 24V
Dual Power Input: Supported
Max Current on Bus: 2A
Diagnosis Function:
Over/under voltage for input 1&2
Over current output on bus
Figure 3.2 AMAX-5001 Application
DC
(±20%)
DC
15