Amax-5001 Application; Amax-5001 Specification - Advantech AMAX-5000 Series User Manual

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

3.1.1

AMAX-5001 Application

The AMAX-5580 controller does not provide power to the right side EtherCAT bus, so
AMAX-5001 must be the first module from the right side to provide independent
power to the EtherCAT bus.
In configuration with large number of IO modules, it is possible to use another AMAX-
5001 to provide extra 2A to the EtherCAT bus. It supply power to the modules follow-
ing on the right side, and isolate from the power on the left side. Please refer to the
following diagram for the detail.
3.1.2

AMAX-5001 Specification

3.1.2.1
General
Certification: CE, FCC class A
Connector: Pluggable 4P+8P push-in terminal (#24~16 AWG)
Enclosure: PC
Power Consumption: 2W @ 24V
Protocol: EtherCAT
Transmission Rate: 100Mbps
Distributed Clock: Default not supported
LED Indicator: PWR, RUN, Power Diagnosis LED
3.1.2.2
Power Input
Rated Voltage: 24V
Dual Power Input: Supported
Max Current on Bus: 2A
Diagnosis Function:
Over/under voltage for input 1&2
Over current output on bus
Figure 3.2 AMAX-5001 Application
DC
(±20%)
DC
11
AMAX-5000 Series User Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents