jcb JS200 Service Manual page 160

Hide thumbs Also See for JS200:
Table of Contents

Advertisement

Section C
5 - 26
Display Monitor (continued)
Hydraulic Oil Temperature
Circuit Diagram
1.
Overheat switch position and the ON signal of the thermostat sensor are OR processed and number 8 is lit.
2.
Overheat switch position and the OFF signal of the thermostat sensor are AND processed and number 8 turns off.
3.
Number 8 is lit on the condition that numbers 1-7 are lit.
4.
When numbers 1-7 are off and the signal for number 8 is transmitted, they light-up in numerical sequence after a 30
second delay.
5.
Number 7 is put out on the condition that number 8 is turned out.
If the signal to switch off number 7 is transmitted when number 8 is lit, the lights-out signal of the Thermostat sensor must
6.
also occur.
7.
When number 8 is lit, 'OVER HEAT' is indicated.
9803/6400
Electrics
Pump Control
Section C
5 - 26
Issue 1