Mounting An Automation Panel 1000 With Clamping Blocks - B&R Panel PC 2100 User Manual

Built-in devices
Hide thumbs Also See for Panel PC 2100:
Table of Contents

Advertisement

Installation • Installation

1.4 Mounting an Automation Panel 1000 with clamping blocks

The Panel PC 2100 with AP1000 display unit is installed in the cutout using clamping blocks. The number of
clamping blocks depends on the display unit.
The following Automation Panel 1000 display units are mounted using clamping blocks:
• 5AP1181.1043-000
• 5AP1182.1043-000
• 5AP1120.1214-000
• 5AP1120.1505-000
• 5AP1180.1505-000
• 5AP1120.1906-000
The thickness of the wall or cabinet plate must be between 2 mm and 10 mm.
A 3 mm hex socket screwdriver is needed to tighten and loosen the screw on the clamping block. The maximum
tightening torque for the screw is 0.5 Nm.
Devices must be installed on a flat, clean and burr-free surface; uneven areas can cause damage to the display
when the screws are tightened or the intrusion of dust and water.
Procedure
1. Insert the device into the front side of the smooth, flat installation cutout. The dimensions for the cutout can
be found in Tab. 13 "AP1000 display units with clamping blocks - Installation diagrams" on page 24. The
number of clamping blocks may vary depending on the display unit. The exact number can be found in Tab.
13 "AP1000 display units with clamping blocks - Installation diagrams" on page 24.
168
Figure 89: Position of the clamping blocks
Panel PC 2100 user's manual V1.11