Where L
= 0.656 μH/m (0.20 μH/ft), if unknown
Cable
B&R device (associated device)
V
oc
I
sc
C
a
L
a
Wiring must follow national regulations and meet all legal requirements.
The B&R device must be installed in a suitable protective housing. For installations in Class I, Division 2 Hazardous
Locations, the housing must be able to withstand one or more Division 2 wiring methods.
Warning!
• Substitution of components may impair suitability for Division 2 or Division 1 hazardous (clas-
sified) locations.
• Do not energize or disconnect the device while the area is known to be hazardous.
• The associated nonincendive field wiring apparatus shall not be connected in parallel unless
permitted by the associated nonincendive apparatus approval.
The B&R device is suitable for use in Class I, Division 2, Groups A, B, C and D. It also offers nonincendive field
wiring for devices in Class I, Division 2, Groups A, B, C and D.
Panel PC 2100 user's manual V1.11
Table 232: Associated nonincendive field wiring apparatus
Standards and certifications • Certifications
-
Associated nonincendive field wiring apparatus (mouse, keyboard)
V
max
I
max
C
+ C
i
Cable
L
+ L
i
Cable