Resistance Measurement Ptc; Table 105: Setting: Resistance Measurement Ptc - Standard Format; Table 106: Setting: Resistance Measurement Ptc - S5-Fb250 Format - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i

Resistance Measurement PTC

4.7.6
4.7.6.1
Standard Format
Table 105: Setting: Resistance Measurement PTC – Standard Format
Resistance
[Ω]
< 0.0
0
200
500
1000
2000
4000
4000.16
4016
≥ 4016.16
4.7.6.2
S5-FB250 Format
Table 106: Setting: Resistance Measurement PTC – S5-FB250 Format
Resistance
[Ω]
< 0.0
0
200
500
1000
2000
4000
4001.6
4016
≥ 4017.6
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
'1000.0000.0000.0000'
0x8000
'0000.0000.0000.0000'
0x0000
'0000.0100.1110.0010'
0x04E2
'0000.1100.0011.0101'
0x0C35
'0001.1000.0110.1010'
0x186A
'0011.0000.1101.0100'
0x30D4
'0110.0001.1010.1000'
0x61A8
'0110.0001.1010.1001'
0x61A9
'0110.0010.0000.1100'
0x620C
'0111.1111.1111.1111'
0x7FFF
Numeric Value
Binary
XFÜ
'1000.0000.0000.0
010'
'0000.0000.0000.0
000'
'0000.0011.1110.1
000'
'0000.1001.1100.0
000'
'0001.0011.1000.1
000'
'0010.0111.0001.0
000'
'0100.1110.0010.0
000'
'0100.1110.0010.1
001'
'0100.1110.0111.0
001'
'0111.1111.1111.1
010'
Status
Byte,
Hex.
Dec.
Hex.
-32768
0x50
0
1250
3125
0x00
6250
12500
25000
25001
0x42
25100
32767
0x60
1)
Hex.
Dec.
0x8002
-32766
0x0000
0
0x03E8
1000
0x09C0
2496
0x1388
5000
0x2710
10000
0x4E20
20000
0x4E29
20009
0x4E71
20081
0x7FFA
32762
Version 1.1.0, valid from FW Version 02
Process Image
Error
Range
LED
On
Underflow
Off
Nominal range
On
Overrange
On
Overflow
Status
Error
Byte,
Range
LED
Hex.
0x50
On
Underflow
Nominal
0x00
Off
range
0x42
On
Overrange
0x60
On
Overflow
Manual
91

Advertisement

Table of Contents
loading