120 Connect Devices
6.3.6
Resistor Bridges (Strain Gauge)
Figure 25: Connection Example: Resistor Bridges (Strain Gauge)
Table 137: Terminal Assignment – Resistor Bridge (Strain Gauge)
Resistor
Bridge
1
2
Manual
Version 1.1.0, valid from FW Version 02
Designation Function
+E1
Measurement input of the reference voltage +U
−E1
Measurement input of the reference voltage −U
+I1
Output reference voltage (+U
−I1
Output reference voltage (−U
+I2
Not used
−I2
Not used
+E2
Measurement input of the bridge voltage +U
−E2
Measurement input of the bridge voltage −U
+E3
Measurement input of the reference voltage +U
−E3
Measurement input of the reference voltage −U
+I3
Output reference voltage (+U
−I3
Output reference voltage (−U
+I4
Not used
−I4
Not used
+E4
Measurement input of the bridge voltage +U
−E4
Measurement input of the bridge voltage −U
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
)
ref
)
ref
)
ref
)
ref
ref
ref
d
d
ref
ref
d
d