Pt100, Pt200, Pt500, Pt1000 (En 60751); Standard Format/Kelvin; S5-Fb250 Format/Kelvin; Table 71: Pt100, Pt200, Pt500, Pt1000 (En 60751) Setting, Standard - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
4.6.1

Pt100, Pt200, Pt500, Pt1000 (EN 60751)

4.6.1.1

Standard Format/Kelvin

The possible numeric range corresponds to the temperature range from +73.2 K
to +1123.2 K, meaning it ranges from +732 to +11232.
Table 71: Pt100, Pt200, Pt500, Pt1000 (EN 60751) Setting, Standard Format/Kelvin
Temperature
[K]
≤ 48.1
48.2
73.1
73.2
1123.2
1123.3
1148.2
≥ 1148.3
4.6.1.2

S5-FB250 Format/Kelvin

Table 72: Pt100, Pt200, Pt500, Pt1000 (EN 60751) Setting, S5-FB250 Format/Kelvin
Temperature
[K]
≤ 47.0
48.0
72.0
73.0
1123.0
1124.0
1148.0
≥ 1149.0
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
'1000.0000.0000.0000'
0x8000
'0000.0001.1110.0010'
0x01E2
'0000.0010.1101.1011' 0x02DB
'0000.0010.1101.1100' 0x02DC
'0010.1011.1110.0000' 0x2BE0
'0010.1011.1110.0001' 0x2BE1
'0010.1100.1101.1010' 0x2CDA
'0111.1111.1111.1111'
0x7FFF
Numeric Value
Binary
XFÜ
'1000.0000.0000.0
010'
'0000.0001.1000.0
001'
'0000.0010.0100.0
001'
'0000.0010.0100.1
000'
'0010.0011.0001.1
000'
'0010.0011.0010.0
001'
'0010.0011.1110.0
001'
'0111.1111.1111.1
010'
Status
Byte,
Hex.
Dec.
Hex.
-32768
0x50
482
0x41
731
732
0x00
11232
11233
0x42
11482
32767
0x60
1)
Hex.
Dec.
0x8002
-32766
0x0181
385
0x0241
577
0x0248
584
0x2318
8984
0x2321
8993
0x23E1
9185
0x7FFA
32762
Version 1.1.0, valid from FW Version 02
Process Image
Error
Range
LED
On
Underflow
On
Underrange
Off
Nominal range
On
Overrange
On
Overflow
Status
Error
Byte,
Range
LED
Hex.
0x50
On
Underflow
0x41
On
Underrange
Nominal
0x00
Off
range
0x42
On
Overrange
0x60
On
Overflow
Manual
73

Advertisement

Table of Contents
loading

Table of Contents