Process Data; Overview Of Sensor Types; Table 22: Process Data, Overview Of Standard Format And S5-Fb250 Format - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

40
Process Image
4.3

Process Data

4.3.1

Overview of Sensor Types

The following table serves as an overview of all of the supported sensor types
with representation in a standard format and in the S5-FB250 format. The
following sections provide detailed information about the individual sensor types.
The information provided in the corresponding tables on the resolution of the
measured values and the resulting raw values ranges is refers to the
manufacturer scaling.

Table 22: Process Data, Overview of Standard Format and S5-FB250 Format

Sensor type Standard
Channel
deactivated
Pt100
Pt200
Pt500
Pt1000
Ni100
Ni120
Ni200
Ni500
Ni1000
Ni1000-
TK5000
TC Type B
TC Type C
TC Type E
TC Type J
TC Type K
TC Type N
TC Type R
TC Type S
TC Type T
Manual
Version 1.1.0, valid from FW Version 02
Measurement
range
-
-
EN 60751
−200 °C...850 °C
DIN 43760
−60 °C...250 °C
DIN EN
+250 °C...+1820 °C
60584-1
DIN 43710
0 °C...+2315 °C
−200 °C...+1000 °C
−210 °C...+1200 °C
−200 °C...+1372 °C
DIN EN
−200 °C... +1300 °C
60584-1
−50 °C ... +1768 °C
−50 °C ... +1768 °C
−200 °C ... +400 °C
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Representation
Two's complement /
sign magnitude
Reso-
Raw value
lution
range
-
-
Celsius
−2000...8500
−600...2500
0.1 °C
2500...18200
0...23150
-2000...10000
-2100...12000
-2000...13720
-2000...13000
-500...17680
-500...17680
-2000...4000
S5-FB250 format
Reso-
Raw value
lution
range
-
-
−200...850
−60...250
1.0 °C
250...1820
0...2315
-200...1000
-210...1200
-200...1372
-200...1300
-50...1768
-50...1768
-200...400

Advertisement

Table of Contents