130 Commissioning
Table 142: Menu Items "Channel 1" ... "Channel 4"
Parameter
Signal type
Sensor type / Measuring
range
Manual
Version 1.1.0, valid from FW Version 02
750-489 4AI RTD/TC/Strain Gauge Ex i
Setting Option / Description
This parameter can be used to set the signal type or
disable the channel.
Channel deactivated
RTD 2-wire
RTD 3-wire
*)
RTD 4-wire
Resistance
Thermocouple
Voltage
This parameter can be used to set the sensor type or
measuring range. The selection of the sensor
type/measuring range is dependent on the signal type
setting.
Pt100
, Pt200, Pt500,
*)
Pt1000, Ni100, Ni120,
Ni200, Ni500, Ni1000,
Ni1000 - TK5000
0-250 Ω, 0-500 Ω,
0-1 kΩ, 0-2 kΩ,
0-4 kΩ, PTC,
Potentiometer
Type B, Type C,
Type E, Type J,
Type K, Type N,
Type R, Type S,
Type T
±30 mV, ±60 mV,
±120 mV, ±250 mV,
±500 mV, ±1000 mV,
±2000 mV,
SG - U
: 2.4 V
,
1)
ref
SG - U
: ±15 mV
2)
,
d
SG - U
: ±30 mV
2)
,
d
SG - U
: ±60 mV
2)
d
WAGO-I/O-SYSTEM 750
The channel is switched off.
0x7FFF is delivered as
process value.
This channel operates using
2-wire connection technology.
This channel operates using
3-wire connection technology.
This channel operates using
4-wire connection technology.
This channel operates using
2-wire connection technology.
Exception: Potentiometer
(operates using 3-wire
connection technology)
This channel operates using
2-wire connection technology.
This channel operates using
2-wire connection technology.
Only available if "RTD 2-wire,"
"RTD 3-wire" or "RTD 4-wire"
was selected as the signal
type
Only available if "Resistance"
was selected as the signal
type
Only available if
"Thermocouple" was selected
as the signal type
Only available if "Voltage" was
selected as the signal type