Table 153: Behavior Of The I/O Module In The Event Of Overflow/Underflow - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

152 Diagnostics

Table 153: Behavior of the I/O Module in the Event of Overflow/Underflow

Overflow/
Underflow
Monitoring
Off
Off
On
On
*)
The different types of monitoring must be enabled/disabled separately.
Manual
Version 1.1.0, valid from FW Version 02
Underrange/
Overrange
Monitoring
*)
*)
Off
On
Off
On
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Behavior of the I/O Module in the Event
of Overflow/Underflow
The upper measurement range
value is output as a process value
No change to the status byte
Error LED does not light up
The upper measurement range
value is output as a process value
Error bit is set
(bit 0: underrange or
bit 1: overrange)
General error (bit 6: general error)
is set
Error LED lights up
Process value is saturated
Error bit is set
(bit 4: underflow or
bit 5: overflow)
General error (bit 6: general error)
is set
Error LED lights up
Process value is saturated
Error bit is set
(bit 4: underflow or
bit 5: overflow)
General error (bit 6: general error)
is set
Error LED lights up