128 Commissioning
Via the [Common] menu item, the following I/O parameters can be set:

Table 141: "Common" Menu Item

Parameter
Temperature unit
Siemens S5 format
Interference frequency
suppression
Factory setting
*)
The settings are transmitted to the I/O module using the [Write] button.
Be aware of process value resolution change!
Activating SIEMENS S5 format changes the process value resolution. Specific
information about resolutions is available in Section "Process Data" > "Overview
of Sensor Types."
Manual
Version 1.1.0, valid from FW Version 02
750-489 4AI RTD/TC/Strain Gauge Ex i
Settings / Description
With this parameter, you can set the desired
temperature unit.
0: Celsius
*)
1: Fahrenheit
2: Kelvin
With this parameter, status information for S5-FB250
can be represented in the lower three bits of the
process value (but only if the corresponding channel
diagnostics are enabled).
On
Off
*)
The input filter is used to suppress interfering mains
frequency signal components. The frequency
depends on the application location and can be set
with module-level granularity.
0: 10 Hz
1: 50 Hz
*)
2: 60 Hz
3: 400 Hz
WAGO-I/O-SYSTEM 750
The process value is output in
degrees Celsius (°C).
The process value is output in
degrees Fahrenheit (°F).
The process value is output in
Kelvin (K).
Bit 0 = overflow (set in the
event of measurement
overrange/underrange)
Bit 1 = error (set in the event
of overflow/underflow)
Bit 2 = always 0
Status indicators not displayed
The mains frequency is 10 Hz
The mains frequency is 50 Hz
(e.g., Europe)
The mains frequency is 60 Hz
(e.g., North America)
The mains frequency is
400 Hz (e.g., marine and
aerospace)